KB2200 Gas Controller |
| Brief description |
KB2200 Gas controller is single-point
gas monitoring system designed by our company. It is used for detecting
gas concentration in the air. Each zone can connect one detector.
The system could connect to detectors for different gases in the
same time. The system adopts MCU as control unit, excellent gas
sensor with high sensitivity and fast response. It will give visual
and audible alarm when the gas concentration reach or exceed the
presetting alarm level to remind you to take effective actions in
time and it could also start the ventilation fan and other equipment
to prevent from accident and explosions.
This controller adopts color LCD display,
window-type interface with keyboard, easy operation. With anti-jamming
software technology, have a high reliability, maintenance. |
| |
Features |
| |
◆ With 32-industrial embedded microprocessors, adopts
embedded real-time operating system and rich functions application
software, to complete the transmitter signal sampling, filtering,
calculation, fault testing, keys Scan, display driver, various alarm
display and alarm control functions.
◆ With an simulate channel input can be connected any 4-20 mA output
equipment
◆ With an simulate channel output, can upload the working signal
to the DCS secondly, and other industrial equipment which can collect
4-20 mA signal
◆ 4 Relay passive switch output, as a trigger signal of external
device can also as a direct driver to use. Each relay can be set
separately, flexible
◆ Can manage different types of gases, different range and different
data units detector
◆ Support dual power input, you can directly use 220 VAC power supply,
can also use the 24 DC power supply, easy to use
◆ Color LCD display, human tips, operating more convenient
◆ Independent zone, random combinations, strong expansibility |
| |
Specifications |
| |
◆ Installation method: Cabinet
◆ Detector model: 4-20mA like our BS01, BS03 etc.
◆ Response time: ≤10s
◆ Indication method: Color LCD display real time data and system
state
LED indicates alarm or fault state
Visual and audio indication for alarm and fault
◆ Contact output: passive contact capacity 3A/AC220V
◆ Working method: continuous working
◆ Working condition: Temperature: -10℃~50℃ Humidity: ≤95%RH
◆ Power supply: AC220V±15% 50Hz±1% or DC24V±25%
◆ Consumption: ≤10W / zone
◆ Detector power supply: DC24V±25%
◆ Dimension per zone: 180mm×42mm×176mm (l×w×h)
◆ Overall dimension: 287mm×490mm×176mm (l×w×h)
◆ Connection cable size: ≥RVVP 4×2.5 mm2
◆ Transform distance: ≤1000m |
|