KB8100 Gas Controller |
| Brief introduction |
| ¡¡¡¡¡ôKB8100, a multi-point detection
panel, is used for detecting gas concentration in the air with high
sensitivity and fast response. It can connect up different detectors
to detect different gases (different extension), and concentrative
control different places with MCU controller and excellent gas sensor.
It will give visual and audible alarm when the gas concentration
exceed the preset level to remind you to take effective measures,
and it will also start up the ventilation fan and other equipments
to avoid explosions, fire and other accidents. |
| |
Features |
| |
¡ô A variety of MPU functions: real-time check of
data, fault detecting, power management, alarm display, alarm indication,
relay outputs etc
¡ô 8 simulate channels for 4-20mA detectors
¡ô 1 signal for RS-485 with the capacity of 32pcs digital detectors
¡ô Simulate channel and digital channel can be used together. The
amount of the detectors is 40.
¡ô It can manage different gas detectors, different level and different
digital unit detectors.
¡ô Intelligent system: easy zero calibration, free relay output
¡ô 8 passive relay contact output, linkage programmer
¡ô Easy to install |
| |
Specifications |
| |
¡ô Installation method: wall-mounted
¡ô Detector model: BS01, BS03, TC100N, TC200
¡ô Response time: < 10s
¡ô Indication method: Large
LCD display real time data and system state Visual
and audio indication for alarm and fault
¡ô Contact output: passive contact capacity 2A/AC220V
¡ô Working method: continuous work
¡ô Working temperature: 0¡æ¡«50¡æ
¡ô Working humidity: £¼95%RH
¡ô Main power: AC220V¡À15%
¡ô Backup power: 2pcs DC12V/7.5AH chargeable battery
¡ô Consumption: ¡Ü10W
¡ô Detector power supply£ºDC24V¡À25%
¡ô Alarm value of backup battery: DC21V¡À1V
¡ô Overall size: 430mm¡Á291mm¡Á104mm
¡ô Connection of detector and panel: ¡ÝRVVP 4¡Á2.5 mm2
¡ô Distance: ¡Ü1000m |
| |
 |
| |