GD-HS10 gas detector is specifically designed for detecting the concentration of flammable, toxic and harmful gases in semiconductor factories. It features high sensitivity, high reliability and low concentration detection. The pump sampling method allows for an intake pipe length of up to 30 meters. The pipe joint adopts a quick-connect joint, making operation and construction convenient. It supports the detection of over 40 types of gases within the industry, such as ammonia, arsine, chlorine, silane, etc., and is suitable for industries like semiconductor wafer manufacturing, liquid crystal panel manufacturing, and photovoltaic panel manufacturing.
GD-HS10 Gas Detector for Semi-conductor Factory
Description
Features
The pump has a long service life and a constant flow rate.
It features a large screen display with rich content.
It supports multiple gas detection functions.
It has built-in low alarm, high alarm, and fault alarm states, and supports 3 groups of relay outputs.
A single network cable can achieve power supply and signal transmission.
Zero-point tracking is available, and alarm thresholds can be configured.
Application
Suitable for industries such as semiconductor wafers, liquid crystal panels and photovoltaic panels, it provides professional-level solutions for the safe monitoring of electronic special gases.
Specifications
| Measuring gas | Gases existing in semi-conductor factories |
| Sensor principle | Catalytic, electrochemical, optical |
| Sampling method | Pump suction |
| Working voltage | DC24V / PoE |
| Power consumption | ≤3.5W |
| Response time | T90≤15s |
| Signal output | Ethernet / 4-20mA / RS485 bus (optional) |
| Installation method | Wall-mounted |
| Working temperature | 0℃~ 40℃ |
| Working humidity | 0~95%RH (no condensation) |
| Air pressure | 86kPa to 106kPa |
| Dimension | 146mmX72mmX123mm |
| Weight | About 750g |
Info Request
For all inquiries, please fill in the form below(* are required) to send us a brief message, and we will get back to you as soon as possible.